VIPA System MICRO
X6: Electronic power
supply

3.2.3 LEDs

Status bar CPU
Status bar
green
yellow
red
Ethernet PG/OP channel
X3/X4
green
yellow
HB400 | CPU | M13-CCF0000 | en | 18-50
The CPU has an integrated power supply. The power supply has to be provided with DC
24V. Via the power supply not only the internal electronic of the CPU is provided with
voltage, but also the electronic from the integrated IO components. The power supply is
protected against polarity inversion and over current.
1
Status bar CPU
2
X3 Ethernet PG/OP channel: LEDs Link/Activity
3
X4 Ethernet PG/OP channel: LEDs Link/Activity
4
X1 DI +0.x: LEDs DI +0.0 ... DI +0.7
5
X1 3L+: LED DC 24V power section supply for on-board DI
6
X2 DO +0.x: LEDs DO +0.0 ... DO +0.7
7
X2 4L+: LED DC 24V power section supply for on-board DO
8
X2 4M: LED on error, overload respectively short circuit at the outputs
9
X5 DI +1.x: LEDs DI +1.0 ... DI +1.7
10 X6 DO +1.x: LEDs DO +1.0 ... DO +1.3
11 X6 1L+: LED DC 24V for electronic section supply
Function
CPU - RUN: CPU is in state RUN without error.
CPU - STOP: CPU is in STOP state.
CPU - system fault: System error occurred.
Function
Ethernet PG/OP channel X3/X4: Link/Activity
Ethernet PG/OP channel X3/X4: Speed
Ä 46