Wiring Periphery Modules - YASKAWA CP 040 RS422/485 Manual

For vipa system slio
Table of Contents

Advertisement

VIPA System SLIO

2.5 Wiring periphery modules

Terminal module terminals
Data
Wiring procedure
HB300 | CP | 040-1CA00 | en | 18-28
7.
After mounting the whole system, to protect the backplane bus connectors at the
last module you have to mount the bus cover, now. If the last module is a clamp
module, for adaptation the upper part of the bus cover is to be removed.
CAUTION!
Do not connect hazardous voltages!
If this is not explicitly stated in the corresponding module description,
hazardous voltages are not allowed to be connected to the corresponding
terminal module!
With wiring the terminal modules, terminals with spring clamp technology are used for
wiring. The spring clamp technology allows quick and easy connection of your signal and
supply lines. In contrast to screw terminal connections this type of connection is vibration
proof.
U
240V AC / 30V DC
max
I
10A
max
Cross section
0.08 ... 1.5mm
Stripping length 10mm
1
Pin number at the connector
2
Opening for screwdriver
3
Connection hole for wire
2
(AWG 28 ... 16)
Basics and mounting
Wiring periphery modules
19

Advertisement

Table of Contents
loading

This manual is also suitable for:

040-1ca00

Table of Contents