YASKAWA VIPA System MICRO Manual page 247

Table of Contents

Advertisement

VIPA System MICRO
Parameter overview
Operating parameters
Output format
Time base
On-delay
HB400 | CPU | M13-CCF0000 | en | 18-50
1
Number of pulses
2
Period duration
3
Pulse duration
4
Pulse pause
Description
Here specify the range of values for the output. The CPU
hereby determines the pulse duration:
n
Per mil
Output value is within 0 ... 1000
Pulse duration = (Output value / 1000) x Period
S7 Analog value:
n
Output value is Siemens S7 analog value 0 ...
27648
Pulse duration = (Output value / 27648) x Period
Here you can set the time base, which will apply for resolu-
tion and range of values of the period duration, minimum
pulse duration and on-delay.
n
1ms: The time base is 1ms
n
0.1ms: The time base is 0.1ms
n
1µs: The time base is 1µs
This parameter is ignored.
Configuration with VIPA SPEED7 Studio
Deployment I/O periphery > Pulse train
Assignment
Per mil
0.1ms
0