Wiring System Slio Periphery - YASKAWA iC9200 Series Operating Manual

Hide thumbs Also See for iC9200 Series:
Table of Contents

Advertisement

iC9200 Series
DC 24V
0V
Remove wire
Remove connector
2.5.2

Wiring System SLIO periphery

HB700 | CPU | PMC921xEx | en | 24-04
1.
Insert through the round connection hole of the according contact your prepared
wire until it stops, so that it is fixed.
�� By pushing the contact spring opens, thus ensuring the necessary contact pres-
sure.
2.
Determine the pin position according to the pin assignment.
3.
Connect the positive pole (+) of your external DC 24V power supply to pin 1 or pin
2.
4.
Connect the minus pole (0V) of your external DC 24V power supply to pin 3 or pin
4.
�� As soon as the CPU is power supplied, the associated LED lights up.
The wire is to be removed by means of a screwdriver with 2.5mm blade width.
1.
Press with your screwdriver vertically at the release button.
�� The contact spring releases the wire.
2.
Pull the wire from the round hole.
You have the option to remove the connector of the power supply, e.g. for a module
change with fixed wiring. For this the connector has a locking lever. The connector is
removed as follows:
1.
Remove connector:
By pressing the release button as shown, the connector is released and can be
removed.
2.
Plug connector:
The connector is plugged by plugging it directly into the release lever. Here, the
locking levers return to their original position.
When using System SLIO modules, you must always mount the power
module 007-1AB00 - DC 24V 10A, because the CPU does not provide a
power section supply due to the system.
Basics and mounting
Wiring > Wiring System SLIO periphery
35