VIPA System MICRO
X2
Function
1
DO 0.7
2
DO 0.6
3
DO 0.5
4
DO 0.4
5
DO 0.3
6
DO 0.2
7
DO 0.1
8
DO 0.0
9
0 V
10
DC 24V
X3/X4: Ethernet PG/OP
channel
X5: DI byte 1
HB400 | CPU | M13-CCF0000 | en | 18-50
Type
LED
green
O
O
O
O
O
O
O
O
I
red
I
8pin RJ45 jack:
The RJ45 jack serves as interface to the Ethernet PG/OP channel.
n
n
This interface allows you to program respectively remote control your CPU and to
access the internal web server.
n
The Ethernet PG/OP channel (X3/X4) is designed as switch. This enables PG/OP
communication via the connections X3 and X4.
n
Configurable connections are possible.
n
DHCP respectively the assignment of the network configuration with a DHCP server
is supported.
n
Default diagnostics addresses: 2025 ... 2040
n
At the first commissioning respectively after a factory reset the Ethernet PG/OP
channel has no IP address. For online access to the CPU via the Ethernet PG/OP
channel, valid IP address parameters have to be assigned to this by means of your
configuration tool. This is called "initialization".
n
Via the Ethernet PG/OP channel, you have access to:
–
Device web page, where you can find information on firmware status, connected
peripherals, current cycle times, etc.
–
WebVisu project, which is to be created in the SPEED7 Studio.
–
PROFINET IO controller or the PROFINET I-Device.
Ä Chap. 4.6 'Hardware configuration - Ethernet PG/OP channel' page 71
Description
Digital output DO 7
Digital output DO 6
Digital output DO 5
Digital output DO 4
Digital output DO 3 / Output channel counter 3
Digital output DO 2 / Output channel counter 2
Digital output DO 1 / PWM 1 / Output channel counter 1
Digital output DO 0 / PWM 0 / Output channel counter 0
4M: GND for onboard DO power section supply / GND PWM
LED (red) is on at short circuit respectively overload
4L+: DC 24V for onboard DO power section supply
Hardware description
Structure > Interfaces
41