YASKAWA VIPA System MICRO Manual page 41

Table of Contents

Advertisement

VIPA System MICRO
X2
Function
1
DO 0.7
2
DO 0.6
3
DO 0.5
4
DO 0.4
5
DO 0.3
6
DO 0.2
7
DO 0.1
8
DO 0.0
9
0 V
10
DC 24V
X3/X4: Ethernet PG/OP
channel
X5: DI byte 1
HB400 | CPU | M13-CCF0000 | en | 18-50
Type
LED
green
O
O
O
O
O
O
O
O
I
red
I
8pin RJ45 jack:
The RJ45 jack serves as interface to the Ethernet PG/OP channel.
n
n
This interface allows you to program respectively remote control your CPU and to
access the internal web server.
n
The Ethernet PG/OP channel (X3/X4) is designed as switch. This enables PG/OP
communication via the connections X3 and X4.
n
Configurable connections are possible.
n
DHCP respectively the assignment of the network configuration with a DHCP server
is supported.
n
Default diagnostics addresses: 2025 ... 2040
n
At the first commissioning respectively after a factory reset the Ethernet PG/OP
channel has no IP address. For online access to the CPU via the Ethernet PG/OP
channel, valid IP address parameters have to be assigned to this by means of your
configuration tool. This is called "initialization".
n
Via the Ethernet PG/OP channel, you have access to:
Device web page, where you can find information on firmware status, connected
peripherals, current cycle times, etc.
WebVisu project, which is to be created in the SPEED7 Studio.
PROFINET IO controller or the PROFINET I-Device.
Ä Chap. 4.6 'Hardware configuration - Ethernet PG/OP channel' page 71
Description
Digital output DO 7
Digital output DO 6
Digital output DO 5
Digital output DO 4
Digital output DO 3 / Output channel counter 3
Digital output DO 2 / Output channel counter 2
Digital output DO 1 / PWM 1 / Output channel counter 1
Digital output DO 0 / PWM 0 / Output channel counter 0
4M: GND for onboard DO power section supply / GND PWM
LED (red) is on at short circuit respectively overload
4L+: DC 24V for onboard DO power section supply
Hardware description
Structure > Interfaces
41