Deployment CPU M13-CCF0000
Setting standard CPU parameters > Parameter CPU
Cycle / Clock memory
Retentive Memory
Interrupts
Time-of-day interrupts
78
n
Update OB1 process image cyclically
This parameter is not relevant.
n
Scan cycle monitoring time
Here the scan cycle monitoring time in milliseconds may be set.
If the scan cycle time exceeds the scan cycle monitoring time, the CPU enters the
STOP mode.
Possible reasons for exceeding the time are:
- Communication processes
- a series of interrupt events
- an error in the CPU program
n
Minimum scan cycle time
This parameter is not relevant.
n
Scan cycle load from Communication
Using this parameter you can control the duration of communication processes,
which always extend the scan cycle time so it does not exceed a specified length.
If the cycle load from communication is set to 50%, the scan cycle time of OB 1
can be doubled. At the same time, the scan cycle time of OB 1 is still being influ-
enced by asynchronous events (e.g. hardware interrupts) as well.
n
Size of the process image input/output area
Here the size of the process image max. 2048 for the input/output periphery may
be fixed (default: 256).
n
OB85 call up at I/O access error
The preset reaction of the CPU may be changed to an I/O access error that
occurs during the update of the process image by the system.
The VIPA CPU is preset such that OB 85 is not called if an I/O access error
occurs and no entry is made in the diagnostic buffer either.
n
Clock memory
Activate the check box if you want to use clock memory and enter the number of
the memory byte.
The selected memory byte cannot be used for temporary data storage.
n
Number of Memory bytes from MB0
Enter the number of retentive memory bytes from memory byte 0 onwards.
n
Number of S7 Timers from T0
Enter the number of retentive S7 timers from T0 onwards. Each S7 timer occu-
pies 2bytes.
n
Number of S7 Counters from C0
Enter the number of retentive S7 counter from C0 onwards.
n
Areas
This parameter is not supported.
n
Priority
Here the priorities are displayed, according to which the hardware interrupt OBs
are processed (hardware interrupt, time-delay interrupt, async. error interrupts).
Priority
n
This value is fixed to 2.
n
Active
By enabling 'Active' the time-of-day interrupt function is enabled.
VIPA System MICRO
HB400 | CPU | M13-CCF0000 | en | 18-50