YASKAWA VIPA System MICRO Manual page 243

Table of Contents

Advertisement

VIPA System MICRO
Parameter overview
Operating parameters
Integration time
max. counting frequency ...
Hardware interrupt
End of measurement
HB400 | CPU | M13-CCF0000 | en | 18-50
1
Integration time
2
Counting pulse
3
SW gate
4
Evaluated frequency
Description
Specify the integration time
Range of values: 10ms ... 10000ms in steps of 1ms
Specify the max. frequency for the corresponding input
Frequency
shortest permissible count pulse
1kHz
400µs
2kHz
200µs
5kHz
80µs
10kHz
40µs
30kHz
13µs
60kHz
6.7µs
100kHz
4µs
Description
Hardware interrupt at end of measurement
Configuration with VIPA SPEED7 Studio
Deployment I/O periphery > Frequency measurement
Assignment
100ms
60kHz
Assignment
de-activated