Basics and mounting
Wiring > Wiring periphery module
Fusing
Remove connector

2.5.2 Wiring periphery module

Periphery module con-
nector
Data
20
n
It is recommended to externally protect the electronic power supply for CPU and
backplane bus with a 3A fuse (fast) respectively by a line circuit breaker 3A character-
istics Z.
n
The power section supply of the internal I/Os is to be externally protected with a 6A
fuse (fast) respectively by a line circuit breaker 6A characteristics Z.
By means of a screwdriver there is the possibility to remove the connectors e.g. for
module exchange with a fix wiring. For this each connector has indentations for unlocking
at the top. Unlocking takes place by the following proceeding:
1.
Remove connector:
Insert your screwdriver from above into one of the indentations.
2.
Push the screwdriver backwards:
ð The connector is unlocked and can be removed.
CAUTION!
Via wrong operation such as pressing, the screwdriver down-
ward the release lever may be damaged.
3.
Plug connector:
The connector is plugged by plugging it directly into the release lever.
For wiring the periphery m module has removable connectors. With the wiring of the con-
nectors a "push-in" spring-clip technique is used. This allows a quick and easy connection
of your signal and supply lines. The clamping off takes place by means of a screwdriver.
U
240V AC / 30V DC
max
I
10A
max
Cross section
0.2 ... 1.5mm
Stripping length 10mm
Use for wiring rigid wires respectively use wire sleeves. When using stranded wires you
have to press the release button with a screwdriver during the wiring.
2
(AWG 24 ... 16)
HB400 | CPU | M13-CCF0000 | en | 16-47