Option: Deployment PROFIBUS communication

Fast introduction

9
Option: Deployment PROFIBUS communication
9.1 Fast introduction
Overview
Steps of configuration
216
For the PROFIBUS communication the use of the optionally available extension module
EM M09 is required. The extension module provides interface X2: MPI(PB) with fixed pin
Ä Chap. 2.4 'Mounting' page 14 The PROFIBUS DP slave is to be config-
assignment.
ured in the hardware configurator from Siemens. Here the configuration happens by the
sub module X1 (MPI/DP) of the Siemens CPU.
To switch the interface X2 MPI(PB) to PROFIBUS functionality you have
to activate the according bus functionality by means of a VSC storage
media from VIPA. By plugging the VSC storage card and then an overall
reset the according functionality is activated.
storage media - VSD, VSC' page 98
The configuration of the PROFIBUS DP slave should be done with the following
approach:
n
Activating bus functionality by means of a VSC
n
Hardware configuration - CPU
n
Use as DP slave
With activating the bus functionality 'PROFIBUS DP slave' by means of a VSC,
the bus functionality 'PROFIBUS DP slave' is unlocked.
n
Transfer of the entire project to the CPU
With the Siemens SIMATIC Manager, the CPU M13-CCF0000 from VIPA
is to be configured as
CPU 314C-2 PN/DP (314-6EH04-0AB0 V3.3)
The PROFIBUS DP slave is to be configured and connected via the sub
module X1 (MPI/DP).
VIPA System MICRO
Ä Chap. 4.15 'Deployment
HB400 | CPU | M13-CCF0000 | en | 18-50