VIPA System MICRO
11.5

TIA Portal - Project transfer

Overview
11.5.1

Transfer via Ethernet

Transfer via Ethernet
Initialization
Transfer
11.5.2

Transfer via memory card

Proceeding
HB400 | CPU | M13-CCF0000 | en | 18-50
There are the following possibilities for project transfer into the CPU:
n
Transfer via Ethernet
n
Transfer via memory card
n
Option: Transfer via MPI
For transfer via Ethernet the CPU has the following interface:
n
X3/X4: Ethernet PG/OP channel via an integrated 2-port switch
So that you may the according Ethernet interface, you have to assign IP address parame-
ters by means of the "initialization".
Ethernet PG/OP channel' page 263
Please consider to use the same IP address data in your project for the CP 343-1.
1.
For the transfer, connect, if not already done, the appropriate Ethernet jack to your
Ethernet.
2.
Open your project with the Siemens TIA Portal.
3.
Click in the Project tree at Online access and choose here by a double-click your
network card, which is connected to the Ethernet PG/OP interface.
4.
Select in the Project tree your CPU and click at [Go online].
5.
Set the access path by selecting "PN/IE" as type of interface, your network card and
the according subnet. Then a net scan is established and the corresponding station
is listed.
6.
Establish with [Connect] a connection.
7.
Click to 'Online è Download to device'.
ð The according block is compiled and by a request transferred to the target
device. Provided that no new hardware configuration is transferred to the CPU,
the entered Ethernet connection is permanently stored in the project as transfer
channel.
The memory card serves as external storage medium. There may be stored several proj-
ects and sub-directories on a memory card. Please regard that your current project is
stored in the root directory and has one of the following file names:
n
S7PROG.WLD
n
AUTOLOAD.WLD
1.
Start the Siemens TIA Portal with your project.
2.
Create a wld file with 'Project è Memory card file è New'.
ð The wld file is shown in the Project tree at "SIMATIC Card Reader" as "Memory
card file".
3.
Copy the blocks from the Program blocks to the wld file. Here the hardware configu-
ration data are automatically copied to the wld file as "System data".
Configuration with TIA Portal
TIA Portal - Project transfer > Transfer via memory card
Ä Chap. 11.3 'TIA Portal - Hardware configuration -
269