Voltage measurement
0 ... 10V
Measuring range
Voltage
(U)
0 ... 10V
> 11.759V
11.759V
10V
5V
0V
-0.8V
< -0.8V

5.3.3 Wiring

X6: DC 24V, AI, DO byte 1
X6
Function
1
1L+
2
1M
3
4
2M
5
AI 0
6
AI 1
Cables for analog signals
HB400 | CPU | M13-CCF0000 | en | 18-50
Decimal
(D)
32767
32511
27648
13824
0
-2212
-32768
Type
LED
green
I
I
I
I
I
I
For the analog signals you have to use isolated cables. With this the interferences can be
reduced. The shield of the analog cables should be grounded at both ends. If there are
potential differences between the cables, a potential compensation current can flow,
which could disturb the analog signals. In this case, you should only ground the shield at
one end of the cable.
Hex
7FFFh
7EFFh
6C00h
3600h
0000h
F75Ch
8000h
Description
1L+: DC 24V for electronic section supply
1M: DC 0V for electronic section supply
Shield
2M: Ground for analog inputs
Analog input AI 0
Analog input AI 1
Deployment I/O periphery
Range
Formulas
overflow
overdrive range
nominal range
D: decimal value
underdrive range
U: voltage value
underflow
Analog input > Wiring