VIPA System MICRO
VIPA specific parameters

4.9 Project transfer

Overview

4.9.1 Transfer via Ethernet

Initialization
Transfer
HB400 | CPU | M13-CCF0000 | en | 18-50
The following parameters may be accessed by means of the properties dialog of the VIPA
CPU.
n
Additional retentive memory
Here enter the number of retentive memory bytes. With 0 the value
'Retentive memory è Number of memory bytes starting with MB0' is set, which is
pre-set at the parameters of the Siemens CPU.
Range of values: 0 (default) ... 8192
n
Additional retentive timer
Enter the number of S7 timers. With 0 the value 'Retentive memory
è Number S7 timers starting with T0' is set, which is pre-set at the parameters of
the Siemens CPU.
Range of values: 0 (default) ... 512
Additional retentive counter
n
Enter the number of S7 counter. With 0 the value 'Retentive memory
è Number S7 counters starting with C0' is set, which is pre-set at the parameters
of the Siemens CPU.
Range of values: 0 (default) ... 512
n
Diagnostics interrupt (default: deactivated)
Diagnostics interrupt DI power section supply
Error: 3L+ (DC 24V DI power section supply) missing respectively <19V
Diagnostics interrupt DO power section supply
Error: 4L+ (DC 24V DO power section supply) missing respectively <19V
Diagnostics interrupt DO short circuit/overload
Error: Short circuit or overload of an digital output respectively current exceeds
0.5A.
n
OB 80 for timer interrupts
Here you can define at which timer interrupt OB the OB 80 (time error) is to be
called.
Range of values: Disabled (default), selection of the corresponding OB
n
PN MultipleWrite
In the activated state, parameter record sets are combined at PROFINET to one
or more Ethernet frames during the connection setup. This speeds up the connec-
tion setup, since a separate Ethernet frame is not used for each parameter record
set.
There is the following possibility for project transfer into the CPU:
n
Transfer via Ethernet
n
Transfer via memory card
Option: Transfer via MPI
n
So that you may access the according Ethernet interface you have to assign IP address
parameters by means of the "initialization".
n
X3/X4: Ethernet PG/OP channel
Ä Chap. 4.6 'Hardware configuration - Ethernet PG/OP channel' page 71
1.
For the transfer, connect, if not already done, the appropriate Ethernet port to your
Ethernet.
2.
Open your project with the Siemens SIMATIC Manager.
Ä Chap. 4.9.3 'Option: Transfer via MPI' page 82
Deployment CPU M13-CCF0000
Project transfer > Transfer via Ethernet
81