YASKAWA VIPA System MICRO Manual page 143

Table of Contents

Advertisement

VIPA System MICRO
5.7.4.2
Interrupt selection
5.7.4.3
Frequency measurement
Parameter hardware con-
figuration
Parameter overview
Operating parameters
Integration time
max. counting frequency ...
Hardware interrupt
End of measurement
HB400 | CPU | M13-CCF0000 | en | 18-50
Via 'Basic parameters' you can reach 'Select interrupt' . Here you can define the inter-
rupts the CPU will trigger. The following parameters are supported:
None: The interrupt function is de-activated.
n
n
Process: The following events of the frequency measurement can trigger a hardware
interrupt (selectable via 'Frequency counting' ):
End of measurement
Diagnostics and process: A diagnostics interrupt is only triggered when a hardware
n
interrupt was lost.
Default values and structure of this dialog box depend on the selected 'Operating mode' .
The following parameters are relevant for frequency measurement, which must be speci-
fied or determined:
1
Integration time
2
Counting pulse
3
SW gate
4
Evaluated frequency
Description
Specify the integration time
Range of values: 10ms ... 10000ms in steps of 1ms
Specify the max. frequency for the corresponding input
Frequency
shortest permissible count pulse
1kHz
400µs
2kHz
200µs
5kHz
80µs
10kHz
40µs
30kHz
13µs
60kHz
6.7µs
Description
Hardware interrupt at end of measurement
Deployment I/O periphery
Frequency measurement > Parametrization
Assignment
100ms
60kHz
Assignment
de-activated
143

Advertisement

Table of Contents
loading

Table of Contents