Deployment PG/OP communication - PROFINET
Deployment as PROFINET I-Device > Steps of configuration
Configure IO devices

7.4 Deployment as PROFINET I-Device

7.4.1 Steps of configuration

Functionality
186
Now the project engineering of the PROFINET IO controller is finished. Please link up
now your IO devices with periphery to your IO controller.
1.
For the project engineering of PROFINET IO device you search the concerning
PROFINET IO device in the hardware catalog at PROFINET-IO and drag&drop it in
the subnet of your IO controller.
2.
Assign a name to the IO device. The configured name must match the name of the
device. Information about setting the device name can be found in the manual of
the IO device.
3.
Enter a valid IP address. The IP address is normally assigned automatically by the
hardware configurator. If this is not desired, you can assign the IP address man-
ually.
4.
Link up the modules of your IO device in the plugged sequence and add the
addresses that should be used by the modules.
5.
If needed, parametrize the modules.
6.
Save, compile and transfer your project.
With firmware version V. 2.4, there is a PROFINET IO controller avail-
able via the Ethernet PG/OP channel, which can be configured as I-
Device.
As soon as you use the PROFINET functionality via the Ethernet
PG/OP channel, this affects the performance and response time of
your system and due to the system the cycle time of the OB1 is
extended by 2ms.
VIPA System MICRO
Ä Chap. 4.9 'Project transfer' page 81
HB400 | CPU | M13-CCF0000 | en | 18-50