Interconnection Diagram; Wiring Notes - YASKAWA VS-616PC5 Series Option Instruction Manual

Isolated 4-20ma output monitor card cm-b2/p
Table of Contents

Advertisement

INTERCONNECTION DIAGRAM

Fig. 4 shows the mounting and interconnection between the inverter and the Isolated Monitor Card
CM-B2/P.

WIRING NOTES

1. Separate the wires for output signals (from the Isolated Monitor Card's terminal block TB1) from
the main circuit wires and other power cables.
2. Use a shielded wire to connect output signals. Connect the wire as shown in Fig. 5 to prevent
noise interference.
Shielded Sheath
C
Failure to observe these precautions may result in equipment malfunctions.
Page 6
L1 (R)
U (T1)
L2 (S)
V (T2)
L3 (T)
W (T3)
VS-616/PC5/P5
AC
AM
2CN
E (G)
Fig. 4 Interconnection Diagram
CAUTION
!
B
A
Armor
Fig.5 Shielded Wire
VS-616PC5/P5 Option Instruction Manual: Isolated Monitor Card CM-B2/P
IM
2
TB2
TB1
1
12
2CN
E
TP1
Isolated Monitor Card
CM-B2/P
A. NEVER connect the wire's shielded sheath when
connecting wires.
B. WRAP insulating tape around shielded areas and
wires where termination occurs.
C. CONNECT the shielded wire end to the Ground-
ing Terminal (E) on the inverter's Terminal E (G).
Current
Output
P
250?