Hardware description
Technical data > Technical data CPU
Order no.
Number of simultaneously utilizable inputs vertical configu-
ration
Input characteristic curve
Initial data size
Technical data digital outputs
Number of outputs
Cable length, shielded
Cable length, unshielded
Rated load voltage
Reverse polarity protection of rated load voltage
Current consumption from load voltage L+ (without load)
Total current per group, horizontal configuration, 40°C
Total current per group, horizontal configuration, 60°C
Total current per group, vertical configuration
Output voltage signal "1" at min. current
Output voltage signal "1" at max. current
Output current at signal "1", rated value
Signal logic output
Output current, permitted range to 40°C
Output current, permitted range to 60°C
Output current at signal "0" max. (residual current)
Output delay of "0" to "1"
Output delay of "1" to "0"
Minimum load current
Lamp load
Parallel switching of outputs for redundant control of a load not possible
Parallel switching of outputs for increased power
Actuation of digital input
Switching frequency with resistive load
Switching frequency with inductive load
Switching frequency on lamp load
Internal limitation of inductive shut-off voltage
Short-circuit protection of output
Trigger level
Number of operating cycle of relay outputs
Switching capacity of contacts
52
M13-CCF0000
16
IEC 61131-2, type 1
16 Bit
12
1000 m
600 m
DC 24 V
ü
20 mA
6 A
6 A
6 A
L+ (-0.8 V)
L+ (-0.8 V)
0.5 A
Sinking output
5 mA to 0.6 A
5 mA to 0.6 A
0.5 mA
2 µs / 30 µs
3 µs / 175 µs
-
10 W
not possible
ü
max. 1000 Hz
max. 0.5 Hz
max. 10 Hz
L+ (-45 V)
yes, electronic
1 A
-
-
HB400 | CPU | M13-CCF0000 | en | 18-50