Deployment CPU M13-CCF0000
Project transfer > Option: Transfer via MPI

4.9.2 Transfer via memory card

Proceeding transfer via
memory card

4.9.3 Option: Transfer via MPI

General
Net structure
82
Set via 'Options è Set PG/PC Interface' the access path to "TCP/IP ® Network
3.
card .... ".
Click to 'PLC è Download' Download ® the dialog "Select target module" is
4.
opened. Select your target module and enter the IP address parameters of the
Ethernet PG/OP channel for connection. Provided that no new hardware configura-
tion is transferred to the CPU, the entered Ethernet connection is permanently
stored in the project as transfer channel.
5.
With [OK] the transfer is started.
System dependent you get a message that the projected system differs
from target system. This message may be accepted by [OK].
® Your project is transferred and may be executed in the CPU after
transfer.
The memory card serves as external storage medium. There may be stored several proj-
ects and sub-directories on a memory card. Please regard that your current project is
stored in the root directory and has one of the following file names:
n
S7PROG.WLD
n
AUTOLOAD.WLD
1.
Start the Siemens SIMATIC Manager with your project
2.
Create with 'File è Memory Card File è New' a new wld file.
3.
Copy the blocks from the project blocks folder and the System data into the wld file.
4.
Copy the wld file at a suited memory card. Plug this into your CPU and start it
again.
ð The transfer of the application program from the memory card into the CPU
takes place depending on the file name after an overall reset or PowerON.
S7PROG.WLD is read from the memory card after overall reset.
AUTOLOAD.WLD is read from the memory card after PowerON.
The flickering of the yellow LED
marks the active transfer. Please regard that your user memory serves for
enough space for your user program, otherwise your user program is not com-
pletely loaded and the red LED
For the transfer via MPI the use of the optionally available extension module EM M09 is
required. The extension module provides the interface X2: MPI(PB) with fixed pin assign-
ment.
Ä Chap. 2.4 'Mounting' page 14
The structure of a MPI net is electrically identical with the structure of a PROFIBUS net.
This means the same rules are valid and you use the same components for the build-up.
The single participants are connected with each other via bus interface plugs and
PROFIBUS cables. Per default the MPI net runs with 187.5kbaud. VIPA CPUs are deliv-
ered with MPI address 2.
VIPA System MICRO
of the status bar of the CPU
of the status bar lights up.
HB400 | CPU | M13-CCF0000 | en | 18-50