Deployment PG/OP communication - PROFINET
Deployment as PROFINET I-Device > Configuration as I-Device
Proceeding

7.4.3 Configuration as I-Device

188
1.
You can find the GSDML files in the download area of www.vipa.com. Load the file
and unzip it on your PC.
2.
Start the Siemens SIMATIC Manager and install via 'Options
è Install new GSD file' both GSD files.
ð After the installation you can find the following virtual devices in the hardware
catalog at 'PROFINET IO è Additional field devices è ...
è VIPA MICRO System':
n
PN I-Device for VIPA CPU
This allows you to configure the Input/output areas in the I-Device of the
VIPA CPU.
n
PN I-Device for higher-level CPU
This allows you to connect the VIPA I-Device to the higher-level IO con-
troller.
It is assumed that a hardware configuration of the CPU exists.
configuration - CPU' page 68
1.
For the project engineering of PROFINET I-Device you have to search the virtual
device 'PN I-Device for VIPA CPU' in the hardware catalog at PROFINET-IO and
drag&drop it in the PROFINET subnet.
2.
Open the properties dialog of the PROFINET IO controller of the CPU by a double-
click at 'PN-IO' and assign the name for the I-Device.
Write down the Name. This name must also be specified as the
'device name' of the I-Device for the higher-level IO controller.
3.
For 'PN-IO' at 'slot' 'X...' assign an IP address via the properties dialog.
VIPA System MICRO
Ä Chap. 4.4 'Hardware
HB400 | CPU | M13-CCF0000 | en | 18-50