Commissioning And Initialization; Configuration Profinet Io Controller - YASKAWA VIPA System MICRO Manual

Table of Contents

Advertisement

VIPA System MICRO

7.3.2 Commissioning and initialization

Assembly and commis-
sioning
Assign IP address param-
eters

7.3.3 Configuration PROFINET IO controller

7.3.3.1
Precondition
HB400 | CPU | M13-CCF0000 | en | 18-50
Deployment as PROFINET IO controller > Configuration PROFINET IO controller
With the Siemens SIMATIC Manager, the CPU M13-CCF0000 from VIPA
is to be configured as
CPU 314C-2 PN/DP (314-6EH04-0AB0 V3.3)
!
1.
Install your System MICRO with your CPU.
2.
Wire the system by connecting cables for voltage supply and signals
3.
Connect your PROFINET IO controller with Ethernet.
4.
Switch on the power supply.
ð After a short boot time, the CP is in idle.
At the first commissioning respectively after an overall reset of the CPU, the
Ethernet PG/OP channel has no IP address.
This function is supported only if the PROFINET IO controller is not yet configured. You
get valid IP address parameters from your system administrator. The assignment of the
IP address data happens online in the Siemens SIMATIC Manager starting with version V
5.5 & SP2 with the following proceeding:
1.
Start the Siemens SIMATIC Manager.
2.
Switch to "TCP/IP -> Network card .... " using 'Options è Set PG/PC interface è '.
3.
Open the dialog for initialization of a station with 'PLC è Edit Ethernet node'.
4.
To get the stations and their MAC address, use the [Browse] button or type in the
MAC address. The Mac address may be found at the front of the CPU.
5.
Choose if necessary the known MAC address of the list of found stations.
6.
Either type in the IP configuration like IP address, subnet mask and gateway. Or
your station is automatically provided with IP parameters by means of a DHCP
server. Depending of the chosen option the DHCP server is to be supplied with
MAC address, equipment name or client ID. The client ID is a numerical order of
max. 63 characters. The following characters are allowed: Hyphen "-", 0-9, a-z, A-Z
7.
Confirm with [Assign IP configuration].
Directly after the assignment the PROFINET IO controller is online reachable using the
set IP address data. You can take the IP address data to your project by means of the
hardware configuration.
To parameterize the PROFINET IO controller of the CPU, the following conditions must
be fulfilled:
n
The PROFINET IO controller is online reachable, this means an initialization was
established.
n
The hardware configuration described before was established and the PROFINET IO
controller is networked.
Deployment PG/OP communication - PROFINET
Ä Chap. 4.4 'Hardware configuration - CPU' page 68