Addressing; Overview; Default Address Assignment Of The I/O Part - YASKAWA VIPA System MICRO Manual

Table of Contents

Advertisement

Deployment CPU M13-CCF0000
Addressing > Default address assignment of the I/O part

4.3 Addressing

4.3.1 Overview

4.3.2 Default address assignment of the I/O part

Sub module
Input
address
AI5/AO2
800
802
Sub module
Input
address
DI24/DO16
136
137
Sub module
Input
address
Counter
816
820
824
828
Sub module
Output
address
DI24/DO16
136
137
Sub module
Output
address
Counter
816
820
824
828
66
To provide specific addressing of the installed peripheral modules, certain addresses
must be allocated in the CPU. This address mapping is in the CPU as hardware configu-
ration. If there is no hardware configuration, depending on the slot, the CPU assigns
automatically peripheral addresses for digital in-/output modules starting with 0 and
analog modules are assigned to even addresses starting with 256.
Access
Assignment
WORD
Analog input channel 0 (X6)
WORD
Analog input channel 1 (X6)
Access
Description
BYTE
Digital input I+0.0 ... I+0.7 (X1)
BYTE
Digital input I+1.0 ... I+1.7 (X5)
Access
Description
DINT
Channel 0: Counter value / Frequency value
DINT
Channel 1: Counter value / Frequency value
DINT
Channel 2: Counter value / Frequency value
DINT
Channel 3: Counter value / Frequency value
Access
Description
BYTE
Digital output Q+0.0 ... Q+0.7 (X2)
BYTE
Digital output Q+1.0 ... Q+1.3 (X6)
Access
Description
DWORD
reserved
DWORD
reserved
DWORD
reserved
DWORD
reserved
VIPA System MICRO
HB400 | CPU | M13-CCF0000 | en | 18-50

Advertisement

Table of Contents
loading

Table of Contents