VIPA System MICRO
Setting standard CPU
parameters
Connection CPU as
PROFINET IO device
HB400 | CPU | M13-CCF0000 | en | 18-50
Device overview:
Module
...
PLC ...
MPI interface...
PROFINET inter-
face
DI24/DO16
AI5/AO2...
Counter...
...
For parametrization of the digital I/O periphery and the technological
functions the corresponding sub modules of the CPU 314C-2 PN/DP
(314-6EH04-0AB0 V3.3) is to be used.
The controlling of the operating modes of the technological functions
happens by means of handling blocks of the user program.
Since the CPU from VIPA is configured as Siemens CPU, so the setting of the non- VIPA
specific parameters takes place via the Siemens CPU. For parametrization click in the
Project arearespectively in the Device overview at the CPU part. Then the parameters of
the CPU part are shown in the Properties dialog. Here you can make your parameter set-
Ä Chap. 4.7 'Setting standard CPU parameters' page 76
tings.
1.
Switch in the Project area to 'Network view' .
2.
After installing the GSDML the IO device for the CPU may be found in the hardware
catalog at Other field devices > PROFINET > IO > VIPA GmbH > VIPA MICRO
PLC. Connect the slave system to the CPU by dragging&dropping it from the hard-
ware catalog to the Network view and connecting it via PROFINET to the CPU.
3.
Click in the Network view at the PROFINET part of the Siemens CPU and enter at
valid IP address data in 'Properties' at 'Ethernet address' in the area 'IP protocol' .
4.
Enter at 'PROFINET' a 'PROFINET device name' . The device name must be
unique at the Ethernet subnet.
TIA Portal - Hardware configuration - CPU
Slot
...
2
2 X1
2 X2
2 5
2 6
2 7
Configuration with TIA Portal
Type
CPU 314C-2PN/DP
MPI/DP interface
PROFINET interface
DI24/DO16
AI5/AO2
Counter
...
261