VACON · 76
Table 13: M1.35 Multi-pump (Multidrive)
Index
Parameter
1.35.21
Autochange Days
Autochange Time
1.35.22
of Day
Autochange:
1.35.23
Frequency Limit
Autochange:
1.35.24
Pump Limit
1.35.25
Bandwidth
1.35.26
Bandwidth Delay
Constant Pro-
1.35.27
duction Speed
1.35.28
Pump 1 Interlock
Flushing Refer-
1.35.29
ence
1
Min
Max
0
127
0.00
P3.3.1.2
1
6
0
100
0
3600
0
100
Maximum
Maximum
reference
reference
LOCAL CONTACTS: HTTP://DRIVES.DANFOSS.COM/DANFOSS-DRIVES/LOCAL-CONTACTS/
Unit
Default
ID
1786
Time
1787
Hz
25:00
1031
1030
%
10
1097
s
10
1098
%
100
1513
DigIN
426
Slot0.1
HZ
50.00
1239
QUICK STARTUP GUIDE
Description
Range: Monday to
Sunday
Range: 00:00:00 to
23:59:59
These parameters
set the level below
which the capacity
must stay for the
autochange to
start.
When the feedback
value stays
between 4.5 and .
5.5 bar, the motor
stays connected.
Setpoint = 5 bar
Bandwidth = 10%
When the feedback
value stays
between 4.5 and
5.5 bar, the motor
stays connected.
When the feedback
is outside the
bandwidth, the
time after which
pumps are added
or removed.
Gives the constant
speed at which the
pump locks, when
the pump goes to
the maximum fre-
quency. The next
pump starts the
regulation in the
multimaster mode.
OPEN = Not active
CLOSED = Active
Gives the frequency
reference when the
flush function is
activated.