PARAMETERS MENU
Table 43: Digital input settings
Index
Parameter
P3.5.1.23
Preset Frequency Selection 2
P3.5.1.24
Motor Potentiometer UP
P3.5.1.25
Motor Potentiometer DOWN
P3.5.1.26
Quick Stop Activation
P3.5.1.27
Timer 1
P3.5.1.28
Timer 2
P3.5.1.29
Timer 3
P3.5.1.30
PID Setpoint Boost
P3.5.1.31
PID Setpoint Selection
P3.5.1.32
External PID Start Signal
External PID Setpoint Selec-
P3.5.1.33
tion
P3.5.1.34
Reset Maintenance Counter 1
P3.5.1.36
Flushing Reference Activation
P3.5.1.38
Fire Mode Activation OPEN
P3.5.1.39
Fire Mode Activation CLOSE
P3.5.1.40
Fire Mode Reverse
P3.5.1.41
Auto-cleaning Activation
P3.5.1.42
Pump 1 Interlock
P3.5.1.43
Pump 2 Interlock
P3.5.1.44
Pump 3 Interlock
P3.5.1.45
Pump 4 Interlock
LOCAL CONTACTS: HTTP://DRIVES.DANFOSS.COM/DANFOSS-DRIVES/LOCAL-CONTACTS/
Default
ID
DigIN Slot0.1 *
421
DigIN Slot0.1
418
DigIN Slot0.1
417
Varies
1213
DigIN Slot0.1
447
DigIN Slot0.1
448
DigIN Slot0.1
449
DigIN Slot0.1
1046
DigIN Slot0.1 *
1047
DigIN Slot0.2
1049
DigIN Slot0.1
1048
DigIN Slot0.1
490
DigIN Slot0.1 *
530
DigIN Slot0.2
1596
DigIN Slot0.1
1619
DigIN Slot0.1
1618
DigIN Slot0.1
1715
DigIN Slot0.1 *
426
DigIN Slot0.1 *
427
DigIN Slot0.1 *
428
DigIN Slot0.1
429
VACON · 139
Description
OPEN = Not active
CLOSED = Active
OPEN = Not active
CLOSED = Active
OPEN = Activated
OPEN = No boost
CLOSED = Boost
OPEN = Setpoint 1
CLOSED = Setpoint 2
OPEN = PID2 in stop mode
CLOSED = PID2 regulating
OPEN = Setpoint 1
CLOSED = Setpoint 2
CLOSED = Reset
OPEN = Fire mode active
CLOSED = No action
OPEN = No action
CLOSED = Fire Mode active
OPEN = Forward
CLOSED = Reverse
OPEN = Not active
CLOSED = Active
OPEN = Not active
CLOSED = Active
OPEN = Not active
CLOSED = Active
OPEN = Not active
CLOSED = Active