QUICK STARTUP GUIDE
Table 13: M1.35 Multi-pump (Multidrive)
Index
Parameter
1.35.1
PID Gain
PID Integration
1.35.2
Time
PID Derivation
1.35.3
Time
Process Unit
1.35.4
Selection
1.35.5
Process Unit Min
Process Unit
1.35.6
Max
Feedback 1
1.35.7
Source Selection
Setpoint 1
1.35.8
Source Selection
Keypad Setpoint
1.35.9
1
LOCAL CONTACTS: HTTP://DRIVES.DANFOSS.COM/DANFOSS-DRIVES/LOCAL-CONTACTS/
Min
Max
0.00
100.00
0.00
600.00
0.00
100.00
1
44
Varies
Varies
Varies
Varies
0
30
0
32
Varies
Varies
Unit
Default
ID
%
100.00
118
s
1.00
119
s
0.00
1132
1
1036
Varies
1033
Varies
1034
2
334
1
332
Varies
0
167
VACON · 73
Description
If the value of the
parameter is set to
100%, a change of
10% in the error
value causes the
controller output to
change by 10%.
If this parameter is
set to, 1,00 s, a
change of 10% in
the error value
causes the control-
ler output to
change by
10.00%/s.
If this parameter is
set to 1,00 s, a
change of 10% in
the error value
during 1.00 s cau-
ses the controller
output to change by
10.00%.
Select the unit of
the process. See
P3.13.1.4
The process unit
value that is the
same as 0% of the
PID feedback sig-
nal.
The process unit
value that is the
same as 100% of
the PID feedback
signal.
See P3.13.3.3
See P3.13.2.6
1