VACON · 124
Table 23: Multi-pump monitoring
Index
Monitoring value
V2.10.1
Motors Running
V2.10.2
Autochange
V2.10.3
Next Autochange
V2.10.4
Operate Mode
V2.10.5
Multi-pump Status
Communication
V2.10.6
Status
Pump (1) Running
V2.10.7
Time
Pump 2 Running
V2.10.8
Time
Pump 3 Running
V2.10.9
Time
Pump 4 Running
V2.10.10
Time
Pump 5 Running
V2.10.11
Time
Pump 6 Running
V2.10.12
Time
Pump 7 Running
V2.10.13
Time
Pump 8 Running
V2.10.14
Time
4
Unit
Scale
ID
1
30
1
1114
h
0.1
1503
1
1505
1
1628
h
0.1
1629
h
0.1
1620
h
0.1
1621
h
0.1
1622
h
0.1
1623
h
0.1
1624
h
0.1
1625
h
0.1
1626
h
0.1
1627
LOCAL CONTACTS: HTTP://DRIVES.DANFOSS.COM/DANFOSS-DRIVES/LOCAL-CONTACTS/
Description
0 = Slave
1 = Master
0 = Not used
10 = Stopped
20 = Sleep
30 = Anti-blocking
40 = Auto-cleaning
50 = Flushing
60 = Soft filling
70 = Regulating
80 = Following
90 = Const. producing
200 = Unknown
0 = Not used (Multi-pump multidrive function)
10 = Fatal communication errors occurred
(or no communication)
11 = Errors occurred (data sending)
12 = Errors occurred (data receiving)
20 = Communication operational, no errors
occurred
30 = Status unknown
MONITORING MENU