Vacon 100 flow Applications Manual page 40

Hide thumbs Also See for 100 flow:
Table of Contents

Advertisement

VACON · 40
Table 10: M1.34 Multi-pump (single drive)
Index
Parameter
1.34.1
PID Gain
PID Integration
1.34.2
Time
PID Derivation
1.34.3
Time
Process Unit
1.34.4
Selection
1.34.5
Process Unit Min
Process Unit
1.34.6
Max
Feedback 1
1.34.7
Source Selection
Setpoint 1
1.34.8
Source Selection
Keypad Setpoint
1.34.9
1
1
Min
Max
0.00
100.00
0.00
600.00
0.00
100.00
1
44
Varies
Varies
Varies
Varies
0
30
0
32
Varies
Varies
LOCAL CONTACTS: HTTP://DRIVES.DANFOSS.COM/DANFOSS-DRIVES/LOCAL-CONTACTS/
Unit
Default
ID
%
100.00
118
s
1.00
119
s
0.00
1132
1
1036
Varies
1033
Varies
1034
2
334
1
332
Varies
0
167
QUICK STARTUP GUIDE
Description
If the value of the
parameter is set to
100%, a change of
10% in the error
value causes the
controller output to
change by 10%.
If this parameter is
set to, 1,00 s, a
change of 10% in
the error value
causes the control-
ler output to
change by
10.00%/s.
If this parameter is
set to 1,00 s, a
change of 10% in
the error value
during 1.00 s cau-
ses the controller
output to change by
10.00%.
Select the unit of
the process. See
P3.13.1.4
The process unit
value that is the
same as 0% of the
PID feedback sig-
nal.
The process unit
value that is the
same as 100% of
the PID feedback
signal.
See P3.13.3.3
See P3.13.2.6

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the 100 flow and is the answer not in the manual?

Questions and answers

Table of Contents

Save PDF