Table 13: M1.35 Multi-pump (Multidrive)
Index
Parameter
SP1 Sleep Fre-
1.35.10
quency Limit
1.35.11
SP1 Sleep Delay
SP1 Wake Up
1.35.12
Level
Multi-pump
1.35.13
Mode
Number of
1.35.14
Pumps
Pump ID Num-
1.35.15
ber
1
Min
Max
0.0
320.0
0
3000
Varies
Varies
0
2
1
8
1
8
LOCAL CONTACTS: HTTP://DRIVES.DANFOSS.COM/DANFOSS-DRIVES/LOCAL-CONTACTS/
Unit
Default
ID
Hz
0.0
1016
s
0
1017
Varies
Varies
1018
0
1785
1
1001
1
1500
QUICK STARTUP GUIDE
Description
The drive goes to
the sleep mode
when the output
frequency stays
below this limit for
longer than is
specified by
parameter Sleep
Delay.
0 = Not used
The minimum
quantity of time
that the frequency
stays below the
sleep level before
the drive stops.
0 = Not used
The wake-up value
of the PID feedback
supervision. Wake-
up Level 1 uses the
selected process
units.
0 = Not used
Selects the Multi-
pump mode.
0 = Single drive
1 = Multifollower
2 = Multimaster
Total number of
motors (pumps/
fans) used in the
Multi-pump sys-
tem.
The order number
of the drive in the
pump system. This
parameter is only
used in multifol-
lower or multimas-
ter modes.