VACON · 340
NOTE!
In the Multimaster and Multifollower modes, it is possible to reset or set the
necessary value only to the counter Pump (1) Running Time. In the Multimaster and
Multifollower modes, the monitoring value Pump (1) Running Time shows the hours
of the pump that is connected to this drive, the ID number of the pump has no
effect.
EXAMPLE
In the Multi-pump (single drive) system, pump number 4 is replaced with a new pump. The
counter value of Pump 4 Running Time must be reset.
1. Select Pump 4 with parameter P3.15.19.3.
2. Set parameter P3.15.19.2 value to 0 h.
3. Push the button-type parameter P3.15.19.1.
4. Pump 4 Running Time is reset.
P3.15.19.3 SET RUNTIME COUNTER: PUMP SELECTION (ID 1088)
Use this parameter to select the pumps for which the runtime counter value is specified by
'Set RunTime: Value' parameter.
If the Multi-pump (single drive) mode is selected, the next selections are available:
0 = All Pumps
1 = Pump (1)
2 = Pump 2
3 = Pump 3
4 = Pump 4
5 = Pump 5
6 = Pump 6
7 = Pump 7
8 = Pump 8
If the Multifollower or Multimaster mode is selected, only the next selection is available:
1 = Pump (1)
NOTE!
In the Multimaster and Multifollower modes, it is possible to reset or to set a
necessary value only for the the Pump (1) Running Time. In the Multimaster and
Multifollower modes, the monitoring value Pump (1) Running Time shows the hours
of the pump that is connected to this drive, the ID number of the pump has no
effect.
EXAMPLE
In the Multi-pump (single drive) system, pump number 4 is replaced with a new pump. The
counter value of Pump 4 Running Time must be reset.
10
LOCAL CONTACTS: HTTP://DRIVES.DANFOSS.COM/DANFOSS-DRIVES/LOCAL-CONTACTS/
PARAMETER DESCRIPTIONS
Need help?
Do you have a question about the 100 flow and is the answer not in the manual?
Questions and answers