• vacon Introduction 1.Introduction 1.1 I NTENDED USE This manual describes the dU/dt filters used with VACON 100 Family AC drives. The ® filter range is designed for the wall-mounted drive up to a current rating of 208 A. 1.2 S...
Page 5
Introduction vacon • CAUTION! Use shielded cables to reduce noise, electromagnetic interference noise and to prevent malfunction in the installation. Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/...
• vacon dU/dt filter range 2.dU/dt filter range 2.1 G ENERAL A pulsed PWM output voltage of an AC drive has typically a high rise time speed (6-8 kV/us) with an unloaded IGBT switch. When the motor cable and the motor are connected, the rise time will drop to 2-3 kV/us.
Page 7
• Figure 1. Change of the voltage shape in winding Voltage stress Figure 2. Voltage pulse reflection The maximum value of the reflected voltage is 2 x DC link voltage, in practice 1.8-1.9 x Udc. The voltage is fully developed at cables that are > 5 m.
Page 8
• vacon dU/dt filter range The filter, the cable and the motor form a complex high frequency circuit, which causes a voltage at the motor with different rise times and peak values depending on the cable length, type etc. Typical voltage peak values as function of cable length are as follows: Figure 3.
Page 9
< 1750 < 0.55 < 1200 < 0.25 < 1800 < 0.35 Table 2. Typical peak voltage Upk and dU/dt values for VACON 100 dU/dt filters. ® Values are based on default cable types given in drive manual. Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/...
• vacon dU/dt filter range 2.2 I NSTALLATION The connection of the dU/dt filter is shown in figure 5. Figure 5. Filter connection In 690 V system the maximum motor cable length for the dU/dt filter is 150 m with default switching frequency and a default cable.
Page 11
• Between the converter output and the unit input (U1, V1, W1), use screened and/or twisted cables. Between the unit output (U2, V2, W2) and the motor, use shielded cables. If you use unscreened cables, make sure that the installation minimises the possibility of cross-coupling with other cables that are carrying sensitive signals.
• vacon Safe operating curves 3 Safe operating curves The safe operating curves for dU/dt filters 130B2835 - 37 are shown in figures 12 and 13. It is assumed that the default cable type has a capacitance of 40 nF/100 m. The values should be scaled in accordance with the actual cable capacitance.
Page 17
Safe operating curves vacon • The safe operating curves for dU/dt filters 130B2838 - 40 are shown in figures 14 and 15. It is assumed that the default cable types have a capacitance of 45 - 55 nF/100 m. The values should be scaled in accordance with the actual cable capacitance. In case of multiple cables, the capacitance is the sum of the cable capacitances.
Page 18
• vacon Safe operating curves The safe operating curves for dU/dt filters 130B2841 - 43 are shown in figures 16 and 17. It is assumed that the default cable types have a capacitance of 55 - 60 nF/100 m. The values should be scaled in accordance with the actual cable capacitance. In case of multiple cables, the capacitance is the sum of the cable capacitances.
Page 19
Safe operating curves vacon • The safe operating curves for dU/dt filters 130B2844 - 46 are shown in figures 18 and 19. It is assumed that the default cable types have a capacitance of 60 - 65 nF/100 m. The values should be scaled in accordance with the actual cable capacitance. In case of multiple cables, the capacitance is the sum of the cable capacitances.
Page 20
• vacon Safe operating curves The safe operating curves for dU/dt filters 130B2847 - 48 are shown in figures 20 and 21. It is assumed that the default cable types have a capacitance of 80 - 85 nF/100 m. The values should be scaled in accordance with the actual cable capacitance. In case of multiple cables, the capacitance is the sum of the cable capacitances.
How to select a filter vacon • 4 How to select a filter The selection of a filter is shown in the tables below. The current rating of the filter must be the same or higher than the matching AC drive current rating.
Page 22
• vacon How to select a filter Table 8. dU/dt filter selection for 525–690 Vac drives 525-690 Vac dU/dt filter selection Enclosure AC drive IP00 IP20 IP23 IP54 size 0007 - 0027 130B2835 130B2836 130B2837 130B2838 130B2839 130B2840 0041 - 0052...
Page 23
How to select a filter vacon • Other than default cable In general, the allowed cable length can be calculated as a ratio between the default cable and actual cable capacitances. As an example, if filter 130B2836 has cable MCMK 3 x 25 + 16 (45 nF/100 m) instead of the default MCMK 3 x 10 +10, the max...
Page 24