PARAMETER DESCRIPTIONS
Fig. 58: The analogue input signal range, selection 0
A. Frequency reference
B. Max freq reference
Selection
Selection name
number
1
2...10V / 4...20mA
Fig. 59: The analogue input signal range, selection 1
A. Frequency reference
B. Max freq reference
LOCAL CONTACTS: HTTP://DRIVES.DANFOSS.COM/DANFOSS-DRIVES/LOCAL-CONTACTS/
A
[Hz]
B
C
0%
50%
0 mA
10 mA
The range of the analogue input signal is 2...10V or 4...20mA
(the dip switch settings on the control board tell which one).
The input signal is 20...100%.
A
[Hz]
B
C
0%
20%
50%
0 mA
4 mA
10 mA
100%
20 mA
C. Min freq reference
D. Analogue input signal
Description
100%
20 mA
C. Min freq reference
D. Analogue input signal