QUICK STARTUP GUIDE
Table 3: M1 Quick Setup
Index
Parameter
I/O Control Refer-
1.22
ence A Selection
Keypad Control Ref-
1.23
erence Selection
Fieldbus Control
1.24
Reference Selection
1.25
AI1 Signal Range
1.26
AI2 Signal Range
1.27
RO1 Function
1.28
RO2 Function
LOCAL CONTACTS: HTTP://DRIVES.DANFOSS.COM/DANFOSS-DRIVES/LOCAL-CONTACTS/
Min
Max
Unit
0
20
0
20
0
20
0
1
0
1
0
74
0
74
Default
ID
Description
The selection of the
frequency reference
source when the con-
trol place is I/O A.
0 = PC
1 = Preset Frequency 0
2 = Keypad Reference
3 = Fieldbus
4 = AI1
5 = AI2
5 = AI1+AI2
7 = PID Reference
8 = Motor Potentiome-
5
117
ter
11 = Block Out.1
12 = Block Out.2
13 = Block Out.3
14 = Block Out.4
15 = Block Out.5
16 = Block Out.6
17 = Block Out.7
18 = Block Out.8
19 = Block Out.9
20 = Block Out.10
The application that
you set with parameter
1.2 gives the default
value.
The selection of the
frequency reference
1
121
source when the con-
trol place is keypad.
See P1.22.
The selection of the
frequency reference
2
122
source when the con-
trol place is fieldbus.
See P1.22.
0= 0..10V / 0..20mA
0
379
1= 2..10V / 4..20mA
0= 0..10V / 0..20mA
1
390
1= 2..10V / 4..20mA
2
11001
See P3.5.3.2.1
3
11004
See P3.5.3.2.1