Operation timing
The operation timing of a speed change by the override function is shown below.
■When override ratio is changed
[Servo program]
[K 1]
INC-1
Axis
1
Travel value
50000 pulse
Speed
10000 pulse/s
[Operation timing]
V
Command speed [pulse/s]
30000
20000
10000
Override ratio setting
1000
device
Servo program start
[St.1040] Start accept flag
OFF
(R: M30080+n/Q: M2001+n)
[St.1049] Speed change "0"
OFF
accepting flag
(R: M30272+n/Q: M2240+n)
(1) When running, speed change starts from the position where override ratio was changed.
(2) When override ratio is set to "0", just as when speed is changed to "0", a deceleration stop is performed and
"[St.1049] Speed change "0" accepting flag (R: M30272+n/Q: M2240+n)" turns ON.
(3) Operation is restarted by changing the override ratio from "0".
(4) Even when the override ratio has been changed at the start, acceleration/deceleration is performed with the
speed including the override ratio.
[K 2]
[K 3]
INC-1
INC-1
Axis
1
Axis
Travel value
10000 pulse
Travel value
Speed
10000 pulse/s
Speed
3000
250
(1)
(1)
ON
(2)
Servo program No.1
1
100000 pulse
10000 pulse/s
0
1500
ON
(3)
Servo
program No.2
7 AUXILIARY AND APPLIED FUNCTIONS
(4)
t
500
Servo
program No.3
7.8 Override Function
7
465