Binary Output - Mitsubishi Electric QJ81DL96 User Manual

Melsec q series, high speed data logger module
Table of Contents

Advertisement

11
FUNCTIONS OF CONFIGURATION TOOL (MODULE SETTINGS)

11.5.14 Binary output

This section explains the settings related to binary file output content.
The "Binary output" screen is only displayed when binary file is selected on the "Logging
type/File format" screen.
Date information
Output date information
In second
In nanosecond
Index
Output indexes
Trigger information
Output trigger flag
11
- 125
11.5 Data Logging Setting
11.5.14 Binary output
POINT
For details on the binary file format, refer to the following section.
 Section 3.7 Binary File Format
Setting screen
Item
Check to log data by attaching time stamps.
Select this to output the date data in second units. (Outputs the accumulated number of
seconds since 1970)
*1
In addition to seconds, select this to output the date data in nanosecond units.
Check to output the index number in the file.
The continuity of logging can be checked by the index.
Check to output the occurrence flag at the data position where the trigger occurred.
*1: Data value is rounded off to 0.1 millisecond unit when the high speed data sampling is specified,
and to 100 millisecond unit when the general data sampling is specified.
Description
-
-
-