Error Code List - Mitsubishi Electric QJ81DL96 User Manual

Melsec q series, high speed data logger module
Table of Contents

Advertisement

18
TROUBLESHOOTING

18.2 Error Code List

This section shows the description of error codes and corrective action.
Error code
0001
System error
H
0002
Response timeout error
H
0041
H
to
System error
0044
H
0045
Processing code error
H
Station No. specification
0046
H
error
0047
Receive data error
H
0048
H
0049
H
004D
H
System error
004E
H
0050
H
0051
H
0055
Channel number error
H
0064
System error
H
0065
Routing parameter error
H
0066
Data send error
H
18
- 7
18.2 Error Code List
POINT
When a 'system error' occurs, consult your local Mitsubishi representative.
Error name
No response has been received from the
other station.
The issued processing code cannot be
processed on the other end.
The specified station number is incorrect.
Data has not been received.
The RUN write setting of the Ethernet
module is disabled.
No routing parameter has been set.
Failed to send the data.
Description
-
-
-
-
Action
• Please consult your local Mitsubishi
representative, explaining a detailed
description of the problem.
• Correct "Access target CPU setting".
• Check the communication cable status
and access target CPU status.
• Adjust the response monitoring time
setting.
 Section 4.5 (3) Response
monitoring time setting (Switch 3 (lower
byte))
• Check if the control CPU of the network
module on the network route to the
access target CPU is set to QCPU(Q
mode).
• Check the routing parameter settings of
the CPU(s) on the access route.
• Check the network on the access route.
• Please consult your local Mitsubishi
representative, explaining a detailed
description of the problem.
• Check the CPU(s) on the access route.
• Correct the station number setting in
"Access target CPU setting".
• Check the CPU(s) on the access route.
• Please consult your local Mitsubishi
representative, explaining a detailed
description of the problem.
• Check the Ethernet module setting of
the access target CPU.
• Please consult your local Mitsubishi
representative, explaining a detailed
description of the problem.
• Set routing parameters on the access
route.
• Check the CPU(s) on the access route.
• Check the network on the access route.
(Continued on the next page)

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sw1dnn-dlutl-e