FUNCTIONS OF CONFIGURATION TOOL (MODULE SETTINGS)
Item
Enable the auto logging
*1
function
Conditions for stopping the
operation of module
Stop due to the maximum
number of files saved
being exceeded
When all of the saved
files exceed a
maximum number
When any of the
saved files exceeds a
maximum number
Stop effected by a timer
Elapsed time
(1) Details on conditions for stopping the operation of module
Check to use the auto logging function.
Check to stop the module operation when the maximum number of data logging, event
logging, or report saved files is exceeded.
Select this to stop the module operation when the maximum number for all data logging,
event logging, and report saved files is exceeded.
In each "Save" setting for data logging, event logging, and reports, set all "Operation
occurring when number of saved files is exceeded" to "Stop".
Select this to stop the module operation when the maximum number of any of the data
logging, event logging, and report saved files is exceeded.
In each "Save" setting for data logging, event logging, and reports, set one or more
"Operation occurring when number of saved files is exceeded" to "Stop".
Check this to stop module operation when the set time elapses after module operation
starts.
Specify the amount of time until the module stops when "Stop effected by a timer" is
specified.
*1: By exporting setting data ( Section 11.3.6) with the auto logging function set to be enabled to
the CompactFlash card, logging can be started without updating settings when the CompactFlash
card is replaced.
(a) Stop due to the maximum number of files saved being exceeded
Specify to stop module operation when the maximum number of data logging,
event logging, or report saved files is exceeded and put the module in a state
where the CompactFlash card can be ejected.
Select the stop condition from the following.
 When the maximum number of all data logging, event logging, and report
saved files is exceeded
 When the maximum number of any of the data logging, event logging, or
report saved files is exceeded
(b) Stop effected by a timer
Specify when you wish to stop module operation after the set amount of time
elapses from the X5 (module operating status) ON state and put the module in a
state where the CompactFlash card can be ejected.
The elapsed time can be set in seconds from 1 to 86400 seconds (24 hours).