13
FUNCTIONS OF CONFIGURATION TOOL (CONFIRMING MODULE OPERATION)

13.1.3 FTP transfer diagnostics

Monitors the results of file transfers to FTP servers.
Operating procedure
Screen display
No.
FTP setting name
Normal complete
Abnormal complete
Error code
FTP resending buffering status
Buffering Number
Buffer usage rate
 Select [Online] [Diagnostics].
 Select the <<FTP transfer diagnostics>> tab.
Item
Displays the index of the FTP setting.
Displays the name of the FTP setting.
Displays the number of times the FTP transfer completed normally.
Displays the number of times the FTP transfer completed in an error.
Displays the newest error code of the FTP transfer.
 Section 18.2 Error Code List
*1*2
Displays the number of data stored in the FTP resend buffer memory.
Current value
*3
Maximum value : The maximum number of buffered data up to the present/Set
Displays the usage rate of the FTP resend buffer memory.
*3
Current value
Maximum value : The maximum usage rate up to the present
Clears the FTP resend buffer memory and cancels resending the FTP transfer.
button
*1: The FTP resend function is supported by the high speed data logger module with a serial number
whose first five digits are '12062' or higher only. "-" is displayed for unsupported modules.
*2: "-" is displayed when "Resend when transfer failed" is not set in the optional setting of the FTP
setting.
*3: The maximum value is cleared when the high speed data logger module is turned OFF.
Description
-
: Current number of buffered data/Set number of buffered data
number of buffering data
: Current usage rate
13.1 Diagnostics