16.6 Operations for Replacing New CompactFlash Card
POINT
(1) If the operation instructed on the previous page is not properly performed,
logging data being processed may be lost, data in the CompactFlash card
being accessed may be damaged, or a file system error may occur.
When an error occurred to a CompactFlash card, refer to the following
section.
 Section 18.3.8 Troubleshooting related to data management,
CompactFlash cards
(2) The settings of high speed data logger module are stored in the CompactFlash
card. Therefore, when the programmable controller CPU is turned ON from
OFF or reset without inserting a CompactFlash card or without writing settings
to a CompactFlash card, the IP address of the high speed data logger module
is reset to the default (192.168.3.3).
If necessary, read the current settings from the CompactFlash card before
ejecting it, and write the settings to the new CompactFlash card as soon as it
is replaced.