11
FUNCTIONS OF CONFIGURATION TOOL (MODULE SETTINGS)
Start condition
1st condition
2nd condition
3rd condition
Start condition
1st condition
2nd condition
3rd condition
(b) Detecting abnormal pattern
Starts monitoring the order from when the start condition is established, and
detects a pattern of conditions established in an order which differs from the 1st
condition, 2nd condition, 3rd condition order.
The trigger occurs when the conditions are established in an order which differs
from the specified order.
Trigger
True
False
True
False
True
False
True
False
(c) Detecting normal pattern
Starts monitoring the order from when the start condition is established, and
detects the pattern of conditions established in 1st condition, 2nd condition, 3rd
condition order.
The trigger occurs when the conditions are established in the specified order.
Trigger
True
False
True
False
True
False
True
False
POINT
(1) If the start condition is established again during the order monitoring period,
monitoring returns to the 1st condition establishment wait state and order
monitoring continues.
(2) If two or more conditions are established simultaneously, the conditions are
considered to have been established in the specified order, so the trigger will
not occur when detecting an abnormal pattern.
Order monitoring period
Order monitoring period
11.5 Data Logging Setting
11.5.11 Trigger (compound condition)
Since the 3rd condition was established
before the 2nd, the trigger occurs and
the order monitoring period ends.
Since the 1st, 2nd, and 3rd conditions were
established in order, the trigger occurs and
the order monitoring period ends.