13
FUNCTIONS OF CONFIGURATION TOOL (CONFIRMING MODULE OPERATION)
Item
Error log
button
Information acquisition status
(1) Operating status
Item
In operation
Stop
Initialization in progress
Stopping
(2) Error status
Item
No error
Continuation error
Stop error
13
- 3
13.1 Diagnostics
13.1.1 Module diagnostics
Displays the history of errors which occurred on the module.
They are deleted by the
Deletes the history of errors which occurred on the module.
Opens a screen which displays the contents of the error log file.
button
Displays communications with the module and the information acquisition
result in the lower left of the screen.
*1: This item is supported by the high speed data logger module with a serial number whose first five
digits are '12062' or higher only.
*2: While an error is occurring, settings cannot be updated.
While an error is occurring, perform "Update settings" while the procedure below.
1. Execute module operation "Stop".
2. Click the
3. Execute module operation "Update settings".
*3: If the same error occurs multiple times, only displays the date and time of occurrence for the first
error which occurred.
Indicates that the module is operating normally.
Indicates that the module is in a stopped state.
The data logging function, event logging function, and report function are not executed
when stopped.
Causes:
• The execution of the auto logging setting is completed.
• "Stop" is executed with module operation.
• File access stop request (Y2) is ON.
• After formatting the CompactFlash card
Indicates that the module is starting.
Displayed immediately after the programmable controller CPU is reset or settings are
written and updated.
Indicates the status when the module is in transition from "In operation" to "Stopped".
Indicates that the module is operating normally without errors.
Indicates the status where the module has a minor error, but is permitted to keep on operating.
Indicates the status where the module has a critical error and is inoperable.
POINT
While the "Update settings" process is being performed, all functions including the
data logging function, event logging function, and report function stop.
Description
*3
button.
button in the "Module status" to clear the error status.
Description
Description
(From the previous page)
Reference
-
-
(3) in this
section
(4) in this
section
Reference
-
Section 11.4.7
Section 13.1.6
-
-