Recipe File Area (Address: 810 To 841) - Mitsubishi Electric QJ81DL96 User Manual

Melsec q series, high speed data logger module
Table of Contents

Advertisement

3
SPECIFICATIONS

3.4.9 Recipe file area (address: 810 to 841)

The status of the recipe execution operation can be checked with this area.
Decimal address
(Hexadecimal)
810 (32A
)
Recipe execution information
H
811 (32B
)
Error code
H
812 (32C
)
Type of recipe execution operation
H
813 (32D
)
Record number
H
814 to 837
Recipe file name
(32E
to 345
)
H
H
838 to 839
Completed recipe execution
(346
to 347
)
operation count
H
H
840 to 841
Failed recipe execution operation
(348
to 349
)
count
H
H
Name
The recipe execution information is stored.
0: Recipe execution operation is not executed
1: Recipe execution operation is executed
The error code which indicates the definition of the
occurred recipe execution operation error is stored.
The type of recipe execution operation is stored.
1: Reading the recipe file from the programmable
controller CPU
100: Writing the recipe file to the programmable
controller CPU
The record number which is the target of recipe
execution operation is stored.
The recipe file name which is the target of recipe
execution operation is stored.
The completed recipe execution operation count after
power-ON is stored.
When executing recipe execution operation to different
recipe files, the total completed recipe execution
operation count is counted.
The failed recipe execution operation count after
power-ON is stored.
3.4.9 Recipe file area (address: 810 to 841)