FUNCTIONS OF CONFIGURATION TOOL (MODULE SETTINGS)
(1) IP address setting
Item
IP address setting
Automatically obtained
Specify
IP address
Subnet mask
Default gateway
11
- 37
11.4 Common Setting
11.4.1 Network setting
Set the IP address necessary for the high speed data logger module network
connection.
Setting screen
Select the method for specifying the IP address of the high speed data logger module.
Select to specify the IP address by automatically acquiring it.
Select to specify the IP address by directly entering it.
Set the IP address of the high speed data logger module in decimal notation.
Set the subnet mask in decimal notation when used. All devices on the same network must use the same
subnet mask.
Set the default gateway in decimal notation.
Only one address can be registered on the high speed data logger module.
*1: "Automatically obtained" cannot be selected in [Common Setting] - [Access target CPU setting]
when "Other station" is specified to the Access target CPU setting and "High Speed Data Logger
Module Ethernet Port" is selected in ÅsNetwork routeÅt tab from [Access source system] - [Module
type].
*2: Can be omitted if only accessing the same network.
POINT
High speed data logger module settings are saved on the CompactFlash card.
Therefore, the IP address of the high speed data logger module returns to the
initial status (192.168.3.3) when turning the power OFF/ON or resetting the
programmable controller CPU without a CompactFlash card inserted in the
module or without the settings written to the CompactFlash card.
When replacing or formatting the CompactFlash card, read the current settings as
necessary and write them after replacing or formatting the card.