Mitsubishi Electric QJ81DL96 User Manual page 598

Melsec q series, high speed data logger module
Table of Contents

Advertisement

18
TROUBLESHOOTING
Error code
CompactFlash card sector
0C74
H
access error
0D80
H
to
0D82
H
100E
System error
H
2000
H
to
20FF
H
4000
H
Errors detected by the access target CPU
to
 QCPU User's Manual (Hardware, Maintenance and Inspection)
4FFF
H
7000
H
Errors detected by the serial communication module
to
 User's manuals of Serial Communication Module and LCPU
7FFF
H
9000
H
System error
9006
H
9008
Send buffer full
H
9202
H
9204
H
920A
H
System error
9920
H
9922
H
9923
H
9E20
Processing code error
H
9E81
Device type error
H
9E82
Device number error
H
Number of device points
9E83
H
error
B000
H
Errors detected in the CC-Link system
to
 User's manual of CC-Link System Master/Local Module
BFFF
H
C000
H
Errors detected in the Ethernet interface module
to
 User's manual of Ethernet Interface Module
CFFF
H
D000
H
Errors detected in the CC-Link IE Field network
to
 User's manual of CC-Link IE Field Network Master/Local Module
DFFF
H
E000
H
Errors detected in the CC-Link IE controller network
to
 Reference manual of CC-Link IE Controller Network
EFFF
H
18
- 31
18.2 Error Code List
Error name
Failed to access to the same sector of the
CompactFlash card in a low.
The CompactFlash card error might occur
due to the power off or CPU module reset
while writing to the Compact Flash card.
The CompactFlash card was mounted
again.
There is no available space in the send
buffer.
The issued processing code cannot be
processed on the other end.
The device type specified for the access
target station is invalid.
The device number specified for the
access target station is out of range.
The specified number of device points for
the access target station is invalid.
Description
-
-
-
(From the previous page)
Action
• Execute the stopping file access before
power off or resetting the CPU module.
• If this error occurs repetitively, replace
the CompactFlash card.
• Please consult your local Mitsubishi
representative, explaining a detailed
description of the problem.
• Please consult your local Mitsubishi
representative, explaining a detailed
description of the problem.
• Check the CPU(s) on the access route.
• Check if the control CPU of the network
module on the network route to the
access target CPU is set to QCPU (Q
mode).
• Please consult your local Mitsubishi
representative, explaining a detailed
description of the problem.
• Check the CPU(s) on the access route.
• Correct the set device type.
• Correct the set device number.
(Continued on the next page)