Mitsubishi Electric QJ81DL96 User Manual page 617

Melsec q series, high speed data logger module
Table of Contents

Advertisement

18
TROUBLESHOOTING
Symptom
A file name is not displayed in
the file list on the "Recipe
Execution Operation" screen.
The file downloaded from the
high speed data logger
module via FTP is old. Its
device values are the ones
before executing the Write
process.)
Recipe file data stored in a
CompactFlash card which is
inserted to a personal
computer are changed.
Check point
Does a recipe file exist in the RECIPE folder of the
CompactFlash card?
Is a unsupported character used for a recipe file
name?
Does more than 257 CSV files exist in the RECIPE
folder of the CompactFlash card?
Have you configured Internet Explorer's
"Temporary Internet files" settings?
Was the 'Write' process performed to the recipe
files by the recipe function?
Was the file access stop performed before
removing the CompactFlash card from the module
disregarding the power ON/OFF status?
18.3.11 Troubleshooting related to recipe function
Corrective action
• Store a recipe file in the RECIPE folder of the
CompactFlash card.
• Use supported characters for a recipe file name.
 Appendix 4.2 Characters usable in file
names, folder (directory) names
• CSV files to be stored in the RECIPE folder of
the CompactFlash card should be less than 256
files.
• Configure Internet Explorer's "Temporary
Internet files" settings.
 Section 10.3 POINT
• Check the recipe execution history.
 Section 15.5.2 (2) Recipe execution
history
• Store the recipe files after performing the file
access stop.
 Section 16.6 (1) Stopping file access
• Use the file browser or FTP transfer function to
store the recipe files.
 Section 13.2 File Browser
 Section 10.3 (2) FTP server function
18.3 Troubleshooting by Symptom
17
(From the previous page)
18
A
18
- 50