TROUBLESHOOTING
Error code
CompactFlash card
0494
H
format error
CompactFlash card check
0495
H
error
CompactFlash card
0496
H
response error
CompactFlash card drive
0497
H
error
CompactFlash card mount
04A0
H
failed
04A1
H
to
System error
04A4
H
04D0
CF card access error
H
04D1
CF card response error
H
0501
CPU error detected
H
0502
APS mismatch
H
0550
H
to
System error
0554
H
0556
H
Setting file error
0557
H
0600
File access stopped error
H
No CompactFlash card
0601
H
error
Unformatted
0602
H
CompactFlash card error
CompactFlash card
0603
H
formatting error
Error name
Failed to format the CompactFlash card.
Failed to check the CompactFlash card.
Access to the CompactFlash card timed
out while waiting for a response from the
card.
The CompactFlash card mount is failed
because a failure was detected.
Or the CompactFlash card drive is in error
status because the CompactFlash card
was ejected during file access.
The CompactFlash card mount is failed
because a failure was detected.
An error occurred when accessing the
file.
Access to the CompactFlash card timed
out while waiting for a response from the
card.
An error was detected in the CPU of the
module mounted station.
APS of the request packet does not match
the one of the response packet.
The start I/O in "Access target CPU
setting" is incorrect.
There is no setting file.
Or the setting file is corrupted.
The high speed data logger module
version is older than the setting file
version.
The access to the CompactFlash card was
attempted when the file access was being
stopped.
Access to the CompactFlash card was
attempted with no card installed.
The access to the unformatted
CompactFlash card was attempted.
The access to the CompactFlash card was
attempted while it was being formatted.
Description
• Check if the CompactFlash card is
inserted properly.
• Replace the CompactFlash card.
• Replace the CompactFlash card.
• Cycle the power of the programmable
controller where the high speed data
logger module is mounted or reset the
programmable controller CPU.
• Stop file access, then remove the
CompactFlash card.
• Check if improper files of folders exist in
the CompactFlash card.
• Check if the CompactFlash card was
inserted properly.
• Replace the CompactFlash card.
• Please consult your local Mitsubishi
-
representative, explaining a detailed
description of the problem.
• Check if the CompactFlash card was
inserted properly.
• Replace the CompactFlash card.
• Check the CPU status of module
mounted station.
• Retry the transmission.
• Correct "Access target CPU setting".
• Please consult your local Mitsubishi
-
representative, explaining a detailed
description of the problem.
• Write the settings again with the
Configuration Tool.
• Replace the CompactFlash card.
• Start the Configuration Tool online from
the high speed data logger module to be
used and write the settings.
• Turn the clear file access stop request
(Y3) ON, and retry after the file access
status (X2) is turned OFF.
• Access after inserting a CompactFlash
card.
• Access after formatting the
CompactFlash card.
18.2 Error Code List
(From the previous page)
Action
(Continued on the next page)
18
- 10
17