FUNCTIONS OF CONFIGURATION TOOL (MODULE SETTINGS)
(6) How to write the time data to the programmable controller CPU after
(Example 1)
(Example 2)
11
- 45
11.4 Common Setting
11.4.2 Time synchronization setting
synchronizing with SNTP
The correct time data after synchronizing with SNTP can be written to the
programmable controller CPU with the program shown in the following figure.
[Program explanation]
1. Set the start I/O address of the high speed data logger module to 0
2. X0B is 'SNTP time synchronization timing'.
 Section 3.3.2 I/O signal details
3. The time writing delay in these programs is a maximum of 2 scan times.
4. D0 to D6 are used as the work area.
.