FUNCTIONS OF CONFIGURATION TOOL (MODULE SETTINGS)
(4) Number of saved files
Item
Number of saved files
Operation occurring when number
of saved files is exceeded
Overwrite
Stop
11
- 139
11.5 Data Logging Setting
11.5.15 Save
Set the maximum number of saved files and the operation when the maximum
number is exceeded.
Specify the maximum number of saved files. (1 to 65535)
Select this to delete files with low numbers and continue data logging when at file switching the
number of saved files has already exceeded the specified number.
When the folder where files with low numbers are deleted becomes empty, that folder is
automatically deleted.
Select this to stop data logging when at file switching the number of saved files has already
exceeded the specified number.
Turns ON the corresponding bit for 'Number of saved files exceeded information' in the buffer
memory's data logging status area.
Delete the latest saved file or the saved file with the lowest number via FTP or with the file
browser of the Configuration Tool to restart data logging.
*1: The storing file and the specified number of saved files are saved on the CompactFlash card.
POINT
The number of saved files is calculated by the saved file number as shown below.
Latest saved file number - Lowest saved file number + 1
Description
-
*1
.