FUNCTIONS OF CONFIGURATION TOOL (MODULE SETTINGS)
11
- 117
11.5 Data Logging Setting
11.5.11 Trigger (compound condition)
(d) Monitoring timeout
After one condition is established, monitors the condition until the next condition is
established.
If the specified monitoring timeout time elapses and the next condition is not
established, this is considered as a timeout and order monitoring ends, and it
again waits for the order start condition to be established.
For the diagram below, after the 1st condition is established, because the 2nd
condition was not established within the monitoring timeout time, this is a
monitoring timeout.
If "Timeout detected" is checked on the "Order" list screen ( (4) in this
section), a trigger occurs at the same time the timeout occurs.
True
Start condition
False
True
1st condition
False
True
2nd condition
False
Trigger
Set "Monitoring timeout" time on the "Order" screen.
 (4) (a) in this section Editing the order conditions
The setting range is shown below.
0.1 to 0.9, 1 to 32767 seconds
When the setting value of "Monitoring timeout" is smaller than that of the sampling
interval, a timeout occurs. When "Timeout detected" is checked, a trigger occurs.
Monitoring timeout time set in the 1st condition row
Monitoring timeout time set in the 2nd condition row
Monitoring timeout
Trigger occurs when "Timeout
detected" is checked