13.4.15 Write Prohibition Setting (Fn010)

Refer to the following section for information on this utility function other than the procedure.
5.1.4 Write Prohibition Setting for Parameters on page 5-8
Panel Display after
Step
Operation
1
2
3
4
5
To enable the change to the setting, turn the power supply to the SERVOPACK OFF and ON again
6
after write protection has been set or cleared.
13.4 Utility Function (Fn) Operations on the Panel Operator
Keys
Press the MODE/SET Key to enter Utility Function
Mode.
MODE/SET
DATA/
Press the UP Key or DOWN Key to display Fn010.
MODE/SET
DATA/
Press the DATA/SHIFT Key for approximately one sec-
ond. The display shown at the left will appear.
MODE/SET
DATA/
Press the UP Key or DOWN Key and set one of the fol-
lowing.
P.0000: Write permitted (default setting)
MODE/SET
DATA/
P.0001: Write prohibited
Press the MODE/SET Key to enter the value. When
the setting has been completed, donE will flash on the
display, and then the display shown on the left will
appear again.
MODE/SET
DATA/
Note: If you set any value other than P.0000 or P.0001, Error
will be displayed.