Noise Filter Wiring and Connection Precautions
Always observe the following precautions when wiring or connecting Noise Filters.
• Separate input lines from output lines. Do not place input lines and output lines in the same
duct or bundle them together.
Incorrect
Noi e
Filter
Grounding plate
Noi e
Filter
Grounding plate
• Separate the Noise Filter ground wire from the output lines. Do not place the Noise Filter
ground wire, output lines, and other signal lines in the same duct or bundle them together.
Incorrect
Noi e
Filter
Grounding plate
• Connect the Noise Filter ground wire directly to the grounding plate. Do not connect the
Noise Filter ground wire to other ground wires.
Incorrect
Noi e
Filter
ERVOPACK ERVOPACK
hielded ground wire
Grounding plate
Correct
Noi e
Filter
Grounding plate
Noi e
Filter
Grounding
plate
eparate the circuit .
Correct
Noi e
Filter
It i OK if the ground
wire i clo e to the
input line .
Grounding plate
Correct
Noi e
Filter
ERVOPACK ERVOPACK
Grounding plate
4.1 Wiring and Connecting SERVOPACKs
4.1.2 Countermeasures against Noise