S-Rdy (Servo Ready) Signal - YASKAWA SGD7S series Product Manual

Sigma-7-series ac servo drive. sigma-7s servopack with analog voltage/pulse train references
Hide thumbs Also See for SGD7S series:
Table of Contents

Advertisement

6.1 I/O Signal Allocations

6.1.7 /S-RDY (Servo Ready) Signal

Setting the Rotation Detection Level
Use the following parameter to set the speed detection level at which to output the /TGON sig-
nal.
• Rotary Servomotors
Pn502
• Linear Servomotors
Pn581
6.1.7

/S-RDY (Servo Ready) Signal

The /S-RDY (Servo Ready) signal turns ON when the SERVOPACK is ready to accept the /S-
ON (Servo ON) input signal.
The /S-RDY signal is turned ON under the following conditions.
• Main circuit power supply is ON.
• There is no hard wire base block state.
• There are no alarms.
• If an absolute encoder is used, the SEN (Absolute Data Request) signal is ON (high level).
• If a Servomotor without a polarity sensor is used, polarity detection has been completed.
• If an absolute encoder is used, the SERVOPACK must be ready to accept the /S-ON (Servo
ON) signal and, if the SEN signal is ON (high level), the output of the position data from the
absolute encoder to the host controller must have been completed.
*
Do not include this condition if the /S-ON (Servo ON) signal is input for the first time after the control power supply
was turned ON. In that case, when the first /S-ON signal is input, polarity detection is started immediately and the
/S-RDY signal turns ON at the completion of polarity detection.
The /S-RDY signal is allocated to CN1-29 and CN1-30 by default.
Type
Output
Note: 1. Use Pn50E = n.X (/S-RDY (Servo Ready) Signal Allocation) to allocate the /S-RDY signal to another
2. Refer to the following section for information on the hard wire base block and the /S-RDY signal.
6-12
Rotation Detection Level
Setting Range
1 to 10,000
Zero Speed Level
Setting Range
1 to 10,000
Signal
Connector Pin No.
CN1-29 and CN1-
/S-RDY
30 (default setting)
connector pin. Refer to the following section for details.
6.1.2 Output Signal Allocations on page 6-8
11.2.7 /S-RDY (Servo Ready Output) Signal on page 11-6
Setting Unit
Default Setting
-1
20
1 min
Setting Unit
Default Setting
1 mm/s
20
Signal Status
ON (closed)
Ready to receive the /S-ON (Servo ON) signal.
Not ready to receive the /S-ON (Servo ON) sig-
OFF (open)
nal.
Speed
Position
Torque
When Enabled
Classification
Immediately
Setup
Speed
Position
Force
When Enabled
Classification
Immediately
Setup
Meaning
*